    EvoHome Hot Water Temperature

    Hi,

    I've recently had Evohome fitted with the hot water kit. Just wondering what experiences people have had with the hot water temp reading.

    Mine currently only seems to go up to 40 despite the water being much hotter than this out the tap. Any ideas on what the issue could be?

    Cheers.
  • top brake
    Automated Home Legend
    • Feb 2015
    • 837

    #2
    Originally posted by theginj View Post
    Hi,

    I've recently had Evohome fitted with the hot water kit. Just wondering what experiences people have had with the hot water temp reading.

    Mine currently only seems to go up to 40 despite the water being much hotter than this out the tap. Any ideas on what the issue could be?

    Cheers.
    Go into installer mode and check the hot water temperature and differential settings, also check the on off times

    Is it a vented or unvented cylinder?
    Has the existing wired thermostat been left in place?

    As always pictures please
    I work for Resideo, posts are personal and my own views.

    Comment

    • theginj
      Automated Home Lurker
      • Mar 2015
      • 3

      #3
      Originally posted by top brake View Post
      Go into installer mode and check the hot water temperature and differential settings, also check the on off times

      Is it a vented or unvented cylinder?
      Has the existing wired thermostat been left in place?

      As always pictures please
      It's a vented cylinder.
      Nope, the thermostat on the boiler has been replaced as you can see in the image. I'm not sure what has happened with the insertion sensor, if its been wired to an existing sensor as the one that came with the kit is still in the box!

      Cheers.



      Attached Files

      Comment

      • top brake
        Automated Home Legend
        • Feb 2015
        • 837

        #4
        The relays and sensor are incorrectly positioned
        Need to be at least 300mm apart
        I work for Resideo, posts are personal and my own views.

        Comment

        • theginj
          Automated Home Lurker
          • Mar 2015
          • 3

          #5
          Originally posted by top brake View Post
          The relays and sensor are incorrectly positioned
          Need to be at least 300mm apart
          Ok. I thought they were all a little close. I've just adjusted the temp and the differential on the water, I'll see how that affects things.

          Thanks for the assistance.

          Comment

          • jonstatt
            Automated Home Guru
            • Feb 2015
            • 111

            #6
            Originally posted by theginj View Post
            Ok. I thought they were all a little close. I've just adjusted the temp and the differential on the water, I'll see how that affects things.

            Thanks for the assistance.

            There are two sensors in the box, one for vented and one for unvented. The one you have left is the one for unvented cylinders. What target temperature was it set to in the service menu? The differential is the amount of "slack" before hot water is switched on again after reaching target temperature. So if the target temperature is 60 degrees and the differential is 10 degrees, that means that once it reaches 60, it will wait until it drops to 50 before it starts heating again.